Customization: | Available |
---|---|
Certification: | ISO9001 |
Shell Material: | Steel Plate |
Still deciding? Get samples of US$ 9999/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Product overview
KYN28A-12(GZS1-12Z) mid-set type metal-clad and metal-enclosed switchgear (hereinafter referred to as switchgear) is a
new type product designed and developed by our company with domestic and international advanced technologies, it is an
ideal upgrading product for replacing the old metal-enclosed switchgear such as KYN1-10, JYN2-10, GBC-10 and so on. Its
advantages as follows:
The cabinet shell is made of al-zinc-coated steel sheet, through CNC processing and multiple bending technique, then assembled with bolts. It is featured with high mechanical strength, neat and elegant appearance, powder coating treated
door, good shock and corrosion resistance. Ingress protection level of the shell reaches IP4X.
Main switch of switchgear can be configured with VD4 vacuum circuit breaker and C3 series fixed type load switch from ABB corporation, also can be configured with many homemade vacuum circuit breakers (such as VS1, VH1, VK, ZN28) instead of overseas similar products.
No matter which circuit breaker selected, make sure that the air insulation distance of its bare conductor is larger than
125mm, and compound insulation is larger than 60mm. The breakers are featured with long service life, high parameters,
less maintenance, small size, etc.
This switchgear is applicable for three-phase power grid of AC 50Hz and class 3.6~12kV, used for electric energy receiving
and distribution, it controls, protects and monitors the circuits, can be used in single bus and single-bus segment system or
dual-bus systems. This switchgear complies with IEC298 Alternating-current metal-enclosed switchgear and controlgear for
rated voltage above 1kV and up to and including 52kV , IEC694 Common specifications for high-voltage switchgear and controlgear, GB3906 Alternating-current metal-enclosed switchgear for rated voltage of 3~36kV, DL404 Indoor AC high voltage switchgear panel, DIN.VDE0670 Alternating-current switchgear for rated voltage above 1kV, etc. It enjoys perfect and reliable anti-misoperation function.
Technical parameters
Technical parameters of switchgear
Item | Unit | Data | |||
Rated voltage Rated frequency Rated current of circuit breaker Rated current of switchgear Rated peak withstand current (4s) Rated peak withstand current (peak) Rated short-circuit breaking current Rated short-circuit making current (peak) |
KV Hz A A KA KA KA KA |
3.6,7.2,12 50 630,1250,1600,2000,2500,3150,4000 630,1250,1600,2000,2500,3150,4000 16,20,25,31.5,40,50,63 40,50,63,80,100,125,160 16,20,25,31.5,40,50,63 40,50,63,80,100,125,160 |
|||
Rated insulation level | 1min power frequency withstand voltage Lightning impulse withstand voltage |
KV KV |
24 40 |
32 60 |
42 75 |
Protection class | The shell is IP4X, and it is IP2X when the compartment door and circuit breaker chamber door are opened |
Technical parameters of VD4 and VS1-12 vacuum circuit breaker
Item | Unit | Data | |||
Rated voltage Rated frequency Rated current of circuit breaker Rated peak withstand current (4s) Rated peak withstand current (peak) Rated short-circuit breaking current Rated short-circuit making current (peak) |
KV Hz A A KA KA KA KA |
3.6,7.2,12 50 630,1250,1600,2000,2500,3150,4000 16,20,25,31.5,40,50,63 40,50,63,80,100,125,160 16,20,25,31.5,40,50,63 40,50,63,80,100,125,160 |
|||
Rated insulation level | 1min power frequency withstand | KV KV |
42 75 |
||
Rated operating sequence Rated short-circuit current breaking times Mechanical life |
Times Times |
O-0.3s-CO-180s-CO 50 2000 |
Mechanical characteristics of VD4 and VS1-12 vacuum circuit breaker
When the circuit breaker is used to control the motor of 3~10kV, must apply metal-oxide arrester if the starting current is smaller than 600A, details should be determined by both users and manufacturer through negotiation. When the circuit breaker is used to disconnect the capacitor bank, rated current of the capacitor bank should not exceed 80% of rated current of circuit breaker.
Item | Unit | Data | |||
Clearance between open contacts Overtravel Phase-to-phase central distance Closing contact bounce time Three-phase opening asynchrony |
mm mm mm ms ms |
11±1 4±0.5 210±0.5,250±0.5,275±0.5 ≤2 ≤2 |
|||
Breaking time at operating voltage of | Max Rating Min |
ms ms |
≤50 ≤50 ≤60 |
||
Closing time Average closing speed Average closing speed Conductive circuit resistance Contact pressure |
ms m/s m/s μΩ N |
≤100 0.9-1.2 0.6-0.8 ≤40 3200±100 |
Technical parameters of operating mechanism
Item | Unit | Value | |
Rated operating voltage | Closing coil | V | DC220,110 |
Closing coil | V | DC220,110 | |
Coil power | Closing coil | W | 245 |
Closing coil | W | 245 | |
Power of energy-storage motor Rated voltage of energy-storage motor Energy-storage time |
W V S |
50 DC220,110 ≤10 |
Main technical parameters of ZN-12 (VHI) vacuum circuit breaker
Item | Unit | Parameter |
Rated voltage Rated frequency Rated current Rated short-circuit breaking current Rated short-circuit making current Rated peak withstand current Rated short-time withstand current Rated short-circuit duration Rated breaking current of single capacitor bank Rated breaking current of back-to-back capacitor bank Power frequency withstand voltage Lightning impulse withstand voltage Rated short-circuit current breaking times Mechanical life |
KV Hz A KA KA KA KA s A A KV KV Times Times |
12 50 1250 31.5 80 80 31.5 4 630 400 42 75 50 1000 |
Rated operating sequence | O-0.3S-CO-180s-CO | |
Opening time Closing time Control voltage Power of closing coil Power of opening coil |
ms ms V VA VA |
Normal service conditions
1.Ambient air temperature: -15ºC~+40ºC;
2.Relative humidity: daily mean not over 95%, monthly mean not over 90%;
3.Altitude: not exceed 4000m;
4.Seismic intensity: not beyond Ms8;
5The installation site should be free of fire, explosive danger, serious pollution, chemical corrosion or severe vibration.
Special requirements beyond above conditions should be determined by both users and manufacturer through negotiation.
Shipping & Packing
Shipping Details: Standard Export carton
Shipping Details: 7-30 day after receing the deposit
Company Information
HONLE Electric Co.Ltd. is the manufacturer which specializes in developing, producing and marketing
industrial electrical products. It has three factories, the first one produces power supply, the second
one produces power transformer, and the third one produces complete set of equipment. As a member of
China Power Supply Society, since HONLE is founded, the company has been insisting on the theoretic
guideline of "science &technology is the first productive force" and holding up brand strategy as the guideline, relying on forwarding power supply technology, perfecting craft and unwearied pursuing to quality. We can
show top quality and set up positive image of enterprisein domestic and foreign market.
Our Service
1.Your inquiry related to our product & price will be replied within 48 hours
2.Well-trained & experienced staff are to answer all your inquiries in English
3.Working time: 8:00am ~17:30pm, Monday to Saturday. (UTC+8)
4.Customized solution & perfect after-sale service
5. Payment: we can accept T/T, L/C, Western Union.
6. For large order, engineer can be sent to your country for on-site mainternace instructions.
FAQ