Model meaning
Overview & features
It is suitable for power systems of AC50Hz and rated working voltage up to and including 10kV, can be used as small and medium sized substation and industrial and mining enterprises, institutions, power distribution transformer equipment and lighting loads.
Iron
The iron core is made of cold-rolled grain-oriented silicon steel sheets with high magnetic conductivity, with inclined joint laminated structure. Section of the core limbs is of multi-class ladder round, with uniform section with that of yoke.
Winding
The winding adopts corrugated oil duct with non-dipping process, bound by shrinkable tape; all windings are of concentric coils; taps of HV winding with corresponding tapping voltage shall be led to the tap switch, and the switch shall be installed on the box cover. Power supply must be cut off first when changing the tapping voltage.
Installation of protection device
Transformers of all capacity specifications have been equipped with pressure relief valve;
Gas relay with alarm and tripping terminals is available on request.
Oil-temperature measurement device
All the transformers are equipped with tube holder for glass-stem thermometer that is set on the top of oil tank, and immersed in oil for about 120±10mm;
1000~2000kVA transformer is equipped with outdoor signal thermometer;
Transformer oil tank
Transformer oil tank is composed of corrugated walls with powder painted surface and reinforced with film. Corrugated cooling fin not only has cooling function, but also has "breathing" function, the elasticity of corrugated cooling fin make it adapt to the change of oil volume due to change of temperature. So this hermetically sealed transformer does not have oil conservator, which decreases the height of transformer.
The transformer adopts vacuum oil-injection technology during encapsulation that thoroughly removes the moisture from transformer, and keeps the transformer oil from contacting the air. This technology also avoid insulation performance reduction or oil aging due to entering of oxygen or moisture, it improves operation reliability of transformer.
Service conditions
Installation height: altitude shall not exceed 1000m
Ambient temperature: -40ºC~40ºC
Dimensions & Schematic
Rated capacity |
Installation dimension (mm) |
kVA |
L |
W |
H |
C1 |
C2 |
200 |
1650 |
870 |
1340 |
550 |
550 |
250 |
1700 |
880 |
1490 |
550 |
550 |
315 |
1750 |
900 |
1560 |
660 |
660 |
400 |
1800 |
1060 |
1600 |
660 |
660 |
500 |
1830 |
1080 |
1660 |
660 |
660 |
630 |
1950 |
1120 |
1690 |
820 |
820 |
800 |
2270 |
1240 |
1840 |
820 |
820 |
1000 |
2310 |
1400 |
1900 |
820 |
820 |
1250 |
2360 |
1460 |
1940 |
820 |
820 |
1600 |
2430 |
1510 |
1990 |
820 |
820 |
Technical parameter
Rated capacity |
Voltage combination |
Connection group |
Loss (KW) |
No-load current |
Short-circuit impedance |
Weight (kg) |
kVA |
HV kV |
High-voltage tapping range |
LV kV |
symbol |
No-load |
On-load |
% |
% |
Oil weight |
Gross weight |
200 |
6
6.3
6.6
10 |
±4×2.5% |
0.4 |
Yyn0
Dyn11 |
0.48 |
3.06 |
1.5 |
4.0 |
260 |
1040 |
250 |
0.56 |
3.60 |
1.4 |
290 |
1160 |
315 |
0.67 |
4.32 |
1.4 |
320 |
1360 |
400 |
0.80 |
5.22 |
1.3 |
350 |
1550 |
500 |
0.96 |
6.21 |
1.2 |
400 |
1820 |
630 |
1.20 |
7.65 |
1.1 |
4.5 |
490 |
2170 |
800 |
1.40 |
9.36 |
1.0 |
600 |
2590 |
1000 |
1.70 |
10.98 |
1.0 |
710 |
3000 |
1250 |
1.95 |
13.05 |
0.9 |
820 |
3630 |
1600 |
2.40 |
15.57 |
0.8 |
840 |
4145 |