Basic Info.

Model NO.
ZX
Poles Number
4
Type
Circuit Breaker
Function
Conventional Circuit Breaker, Circuit-Breaker Failure Protection, Overcurrent Protection, OVP(Overvoltage Protection), RCCB
Certification
CCC
Applications
Substation Industrial /Distribution Networks
Transport Package
Wooden Case
Trademark
HONLE
Origin
Zehjiang, China
HS Code
8546201000
Production Capacity
5000PCS/Year

Product Description

PRODUCT INTRODUCTION
       The ZX switch combines solid cycloaliphatic- epoxy vacuum interrupters with a reliable, lightweight  operating mechanism that utilizes a magnetic actuator to provide a lifetime of trouble- free operation.  The solid polymer system does not rely on a gaseous, liquid, or foam dielectric. The ZX switch is highly resistant to ozone, oxygen,moisture, contamination, and ultraviolet light.

 Switch operations are programmed in an electronic control with accurate characteristics and a host of   advanced features. When system requirements change, program settings are easily altered with no sacrifice of accuracy or consistency.


Long life and low maintenance
Magnetic actuators and superior design allow our reclosers to operate for a rated 10,000 full load operations.  Less moving parts = less maintenance for 25 years.

High reliability
We designed a simple, magnetically actuated     operating mechanism that could dependably operate with only one moving part.  Vacuum interrupter technology make ZX recloser with  maximum reliability and minimal maintenance.
Environmentally friendly.

Optimized measurement
Reclosers are equipped with current transformer and voltage sensors in each bushings to measure current and voltage, It makes the recloser an ideal device for self-healing loop automation solutions.

Microprocessor based controller
Controller provides more enhanced functions in protection,   monitoring, metering, communication and recorder, and can also support your power distribution system to be more  reliable.
 
38kv Three Phase Automatic Recloser for Substation
38kv Three Phase Automatic Recloser for Substation
38kv Three Phase Automatic Recloser for Substation
 
38kv Three Phase Automatic Recloser for Substation
38kv Three Phase Automatic Recloser for Substation
38kv Three Phase Automatic Recloser for Substation



15.5kV  50/60HZ
Item Unit ZX15-630-12-N ZX15-800-12-N ZX15-630-16-N ZX15-800-16-N
Rated continuous current Ir A 630 800 630 800
Rated duration of short-circuit Tk S 3 3 3 3
Rated short-circuit breaking current Isc kA 12.5 12.5 16 16
Rated short-circuit making current Ima kA 31.5 31.5 40 40
Rated lightning impulse withstand voltage Up kV 110 110 110 110
Rated short-duration P.F.withstand voltage Ud kV 50 50 50 50
Impedance  μ between connections μΩ 60 60 60 60
Creepage distance,phase-to-earth mm 850 850 850 850
Clearance,phase-to-phase mm 320 320 320 320
Minium clearance,phase-to-earth mm 270 270 270 270
Weight kg 130 130 130 130
Line charging current A 2 2 2 2
Cable charging current A 10 10 10 10
Max.interrupting time/max.closing time ms 40/60 40/60 40/60 40/60
 
27kV
50/60Hz

ZX27-630-12-N
ZX27-800-12-N
ZX27-630-16-N
ZX27-800-16-N
ZX27-630-16-H
ZX27-800-16-H
Ir
A
630
800
630
800
630
800
Tk
s
3
3
3
3
3
3
Isc
kA
12.5
12.5
16
16
16
16
Ima
kA
31.5
31.5
40
40
40
40
Up
kV
125
125
125
125
170
170
Ud
kV
60
60
60
60
70
70

μΩ        mm
60         850
60         850
60         850
60         850
60       1290
60       1290

mm
320
320
320
320
320
320

mm
270
270
270
270
350
350

kg
140
140
140
140
150
150

A
5
5
5
5
5
5

A        ms
25       40/60
25       40/60
25       40/60
25       40/60
25       40/60
25       40/60
 
38kV
50/60Hz
ZX38-630-12-N
ZX38-800-12-N
ZX38-630-16-N
ZX38-800-16-N
Ir
A
630
800
630
800
Tk
s
3
3
3
3
Isc
kA
12.5
12.5
16
16
Ima
kA
31.5
31.5
40
40
Up
kV
170
170
170
170
Ud
kV
70
70
70
70

μΩ
60
60
60
60

mm
1290
1290
1290
1290

mm
320
320
320
320

mm
350
350
350
350

kg
150
150
150
150

A
5
5
5
5

A        ms
40       40/60
40       40/60
40       40/60
40       40/60

Dimension Drawings
    A B C D E F
15.5kV mm 460 380 850 508 270 970
27kV mm 460 380 850 508 270 970
38kV mm 512 380 970 590 270 970
38kv Three Phase Automatic Recloser for Substation
38kv Three Phase Automatic Recloser for Substation


                   pole mount                                    Substation mount
                       

 

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now

You Might Also Like

360° Virtual Tour

Diamond Member Since 2014

Suppliers with verified business licenses

Rating: 5.0/5
Registered Capital
16.52 Million USD
Plant Area
35000 square meters
Management System Certification
ISO9001:2015, ISO14001:2015, ISO45001:2018 certificate