Customization: | Available |
---|---|
Certification: | VDE, CCC, ISO9001 |
Shell Material: | Stainless Steel |
Still deciding? Get samples of US$ 5500/Piece
Order Sample
|
Shipping Cost: | Contact the supplier about freight and estimated delivery time. |
---|
Payment Methods: |
|
---|---|
Support payments in USD |
Secure payments: | Every payment you make on Made-in-China.com is protected by the platform. |
---|
Refund policy: | Claim a refund if your order doesn't ship, is missing, or arrives with product issues. |
---|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
KYN61 Series 40.5kV MV Withdrawable Metal-Clad Switchgear
SUMMARY
KYN61-40.5 Series switchgear panel is a MV air-insulated switchgear (AlS)for primary distribution,with vacuum circuit- breaker has been designed for the various operatingrequirements in public and industrialmedium-voltage distribution systems.
This panel applies to 27~40.5kv 3 phase AC 50Hz/60Hz network for receiving and distributing power energy and also for control,
monitor and protection.
It can be arranged for single bus,single-bus sectionalizing system.It accords to IEC62271-200 <<AC Metal Enclosed Switchgear and Control Equipment above 1kv and below 52kv>>,IEC694<<Standard Common Clause for HV Switchgear and Control Equipment>>,GB3906<<3~35KV AC Metal Enclosed Switchgear>>,DL404<<Order Specification for Indoor AC HV Switchgear>>,DIN.VDE0670<<AC Switchgear at Rated Voltage over 1kV>>and so on.It has perfect and reliable prevention function against false-operation.
OPERATING CONDITIONS
Normal operating conditions,according to the IEC International Standards listed below,for indoor switchgear.
Ambient air temperature
·Less than or equal to 40ºC
·Less than or equal to 35ºC on average over 24 hours
·Greater than or equal to -5°C(-25°C on request)
Altitude
·Less than or equal to 1000 m;
·Above 1000 m,a derating coefficient is applied(please consult us)
Atmosphere
·No dust,smoke,or corrosive,or inflammable gas and vapor, or salt
·Earthquake intensity:Magnitude 8
Humidity
·Average relative humidity over a 24 hour period≤95% ·Average relative humidity over a 1 month period≤90%
·Average vapor pressure over a 24 hour period≤2.2 kPa ·Average vapor pressure over a 1 month period ≤1.8 kPa
Features
1.Provides middle rolling and floor roiling two different withdrawble types,can meet all our customers' technical
requirements and operating features.
2.Reliable "anti-5" mechanical latch,convenient and safe maintenance.
3.Both VCB of ZN85-40.5/VS1-40.5 developed by our company and VD4,VB2 and 3AH manufactured by other companies around the world can be matched with the switchgear.
Item | Unit | Data | ||
Rated voltage | KV | 27,33,36,38,40.5 | ||
Rated |
1min.PE withstand voltage (phases to ground/gaps) |
KV | 85/95 | |
insulation level | Lightning impulse withstand voltage (phases to ground/gaps) | KV | 185/215 | |
Rated frequency | Hz | 50/60 | ||
Rated current | A | 630,1250,1600,2000,2500,3150 | ||
Rated short-time withstand current(4s) | KA | 16,20,25,31.5,40,50 | ||
Rated peak withstand current | KA | 40,50,63,80,100,125 | ||
Protection class | Enclosure:IP4X,IP2X(VCB Door opened) | |||
Outine dimension(widthxdepthxheight) | mm | 1400(1200)x2800(2600)x260(2400) | ||
weight | kg | 1300-1600 |