Item | Unit | Parameter |
Rated voltage | kV | 10 |
Highest working voltage | kV | 12 |
Rated frequency | Hz | 50/60 |
Main busbar rated current | A | 630 |
Main loop,earthing loop rated short time withstand current | kA/s | 20/3 |
Main loop,earthing loop rated peak withstand current | kA | 50 |
Main loop,earthing loop rated short circuit making current | kA | 50 |
Load break switch full capacity breaking time | Times | 100 |
Fuse breaking current | kA | 31.5-50 |
Mechanlcal life | Times | 2000 |
Rated transfer current | A | 1700 |
1min P.F. Withstand(virtral value),phase to phase, earth/across open contacts | kV | 42/48 |
Lightning impulse withstand voltage(peak) phase to phase, earth/across open contacts | kV | 75/85 |
Secondary loop 1min P.F. Withstand | kV | 2 |
Protection degree | IP3X |
Width of circuit breaker panel | mm | 750 |
Other width of panel | mm | 375/500 |
Height | mm | 1600/1850 |
Depth | mm | 980 |
Height of LVcase | mm | 450 |