KYN61-40.5 Series switchgear panel is a MV air-insulated switchgear (AlS)for primary distribution,with vacuum circuit- breaker has been designed for the various operatingrequirements in public and industrialmedium-voltage distribution systems. This panel applies to 27~40.5kv 3 phase AC 50Hz/60Hz network for receiving and distributing power energy and also for control, monitor and protection. It can be arranged for single bus,single-bus sectionalizing system.It accords to IEC62271-200 <<AC Metal Enclosed Switchgear and Control Equipment above 1kv and below 52kv>>,IEC694<<Standard Common Clause for HV Switchgear and Control Equipment>>,GB3906<<3~35KV AC Metal Enclosed Switchgear>>,DL404<<Order Specification for Indoor AC HV Switchgear>>,DIN.VDE0670<<AC Switchgear at Rated Voltage over 1kV>>and so on.It has perfect and reliable prevention function against false-operation. |
Normal operating conditions,according to the IEC International Standards listed below,for indoor switchgear.
Ambient air temperature
·Less than or equal to 40ºC
·Less than or equal to 35°ºC on average over 24 hours
·Greater than or equal to-5°C(-25°C on request)
Altitude
·Less than or equal to 1000 m;
·Above 1000 m,a derating coefficient is applied(please consult us)
Atmosphere
·No dust,smoke,or corrosive,or inflammable gas and vapor, or salt
·Earthquake intensity:Magnitude 8
Humidity
·Average relative humidity over a 24 hour period≤95% ·Average relative humidity over a 1 month period≤90%
·Average vapor pressure over a 24 hour period≤2.2 kPa ·Average vapor pressure over a 1 month period ≤1.8 kPa
·Provides Middle Rolling and Floor Roiling two different withdrawble types,can meet all our customers'technical
Item | Unit | Data | ||
Rated voltage | KV | 27,33,36,38,40.5 | ||
Rated |
1min.PE withstand voltage (phases to ground/gaps) |
KV | 85/95 | |
insulation level | Lightning impulse withstand voltage (phases to ground/gaps) | KV | 185/215 | |
Rated frequency | Hz | 50/60 | ||
Rated current | A | 630,1250,1600,2000,2500,3150 | ||
Rated short-time withstand current(4s) | KA | 16,20,25,31.5,40,50 | ||
Rated peak withstand current | KA | 40,50,63,80,100,125 | ||
Protection class | Enclosure:IP4X,IP2X(VCB Door opened) | |||
Outine dimension(widthxdepthxheight) | mm | 1400(1200)x2800(2600)x260(2400) | ||
weight | kg | 1300-1600 |