Product Description
FLRN36 indoor AC high-voltage load break switch-fuse combination (combination in short)is a comprehensive and new combination app aratus produced on the bases of the mature experience in domestic and abroad. It is a complement apparatus of HXGN15-12/24 AC metal-enclosed ring main unit and it meet requirement of users in different power system. It has the advantages such as simple structure, easy maintenance, strong arc-extinction capability, high gap insulating level and high reliability. It accords with IEC62271-105, GB16926 & GB/T 11022 standards.
Ambient condition
1. Altitude: ≤1000m;
2. Ambient temperature: -25ºC ~+40ºC ;
3. Relative humidity: daily average≤95% , monthly average≤90% ;
4. Earthquake intensity: ≤8 degree;
5. Occasions without flammable and explosive matter, without corrosive chemical and frequent severe vibration
Product Parameters
Item NO. |
Name |
Unit |
Technical parameters |
Load break switch panel |
1 |
Rated Voltage Un |
kV |
12 |
24 |
36 |
2 |
Rated Frequency |
Hz |
50 |
50 |
50 |
3 |
Rated Current |
A |
630 |
630 |
630 |
4 |
Rated Load Breaking Current |
A |
630 |
630 |
630 |
5 |
Rated Short Time Withstand Current(rms) |
kA |
20 |
20 |
20 |
6 |
Rated Short Time Duration |
s |
3 |
3 |
3 |
7 |
Rated Peak Withstand Current |
kA |
50 |
50 |
50 |
8 |
Rated Closed Switch - Off Current |
A |
630 |
630 |
630 |
9 |
Rated Cable Charging Breaking Current |
A |
10 |
10 |
10 |
10 |
Rated Active Load Breaking Current |
A |
630 |
630 |
630 |
13 |
Earthing Switch 2s Short Time Withstand Current |
kA |
20 |
20 |
20 |
14 |
Rated Short-Circuit Current Making Times |
times |
2 |
2 |
2 |
15 |
Rated Current Breaking Times |
times |
10 |
10 |
10 |
16 |
Mechanical Endurance |
Load Break Switch |
times |
3000 |
3000 |
3000 |
Earthing Switch |
times |
2000 |
2000 |
2000 |
17 |
SF6 gas anual leakage rate≤ |
/year |
0.10% |
0.10% |
0.10% |
18 |
Rated Insulation Level |
Unit |
Technical parameters |
1min Power Frequency withstand voltage(rms) |
On isolating distance |
kV |
48 |
60 |
110 |
Phase to Phase |
kV |
42 |
50 |
85 |
Phase to Earth |
kV |
42 |
50 |
85 |
Lightning impulse withstand voltage(peak) |
On isolating distance |
kV |
85 |
145 |
215 |
Phase to Phase |
kV |
75 |
125 |
185 |
Phase to Earth |
kV |
75 |
125 |
185 |