Customization: | Available |
---|---|
Breaking Capacity: | High Voltage Circuit Breakers |
Operation: | Energy-storage Type |
Still deciding? Get samples of US$ 1200/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Product performance standards
The manufacture of ZW7A outdoor high voltage AC vacuum circuit breaker complies with the following standards and specifications:
IEC 62271-100 High Voltage AC Circuit Breaker.
GB/T 11022-2011 High-voltage switchgear and control equipment standard common technology.
GB 1984 high voltage AC circuit breaker.
GB 311.1 Insulation coordination of high-voltage power transmission and transformation equipment.
The main technical parameters
Project | Unit | Reference | |
Rated voltage | KV | 12 | |
Rated insulation level |
Lightning impulse withstand voltage | KV | 75 |
1min power frequency withstand voltage | KV | 42 | |
Rated frequency | HZ | 50/60 | |
Rated current | A | 630/1250 | |
Rated short-circuit breaking current | KA | 16/20/25 | |
Rated short-circuit making current (peak value) | KA | 40/50/63 | |
Rated short-time withstand current | KA | 16/20/25 | |
Rated peak withstand current | KA | 40/50/63 | |
Rated short-circuit duration | s | 4 | |
Breaking times of rated short-circuit current | Times | 30 | |
Mechanical life | M2 Class | ||
weight | kg | 145 |
Project | Unit | Reference |
Contact opening distance | mm | 9±21 |
Contact overtravel | mm | 3±1 |
Average closing speed | m/s | 0.6±0.2 |
Average opening speed | m/s | 1.2±0.2 |
Bounce time of contact closing | ms | ≤2 |
Different timing of contact closing and opening | ms | ≤2 |
Loop resistance of each phase | μ Ω |
Switch ≤200 Isolation ≤50 |
Dynamic and static contact allowable wear cumulative thickness | mm | 3 |
Operating mechanism
The spring operating mechanism of the circuit breaker stores energy through manual operation, no need. Any external power supply is required, which is convenient and reliable. After the energy storage is in place, it can be operated by closing and opening
The handle is used for closing operation. When in the closing position, it can be accessed directly through the closing and opening handles. The opening operation is performed, and no energy storage is required for each opening operation.