Cabinet size(W×D×H) | Circuit breaker cabinet | Cable connection cabinet | PT cabinet |
Top expansion | 420×850×1950 | 420×850×1950 | 600×850×1950 |
Side expansion | 420×850×2000 | 420×850×2000 | 600×850×1950 |
Rated voltage | kV | 12 |
Rated current | A | 630 |
Arc extinguishing method | Vacuum switch tube | |
Insulation method | Pure air or nitrogen | |
Rated short circuit breaking current | kV | 20 |
Rated short circuit breaking times | Times | 30 |
Rated short-circuit closing current(peak) |
KV | 50 |
Rated short-time withstand current3s(rms) | kA | 20(Main circuit),17,4(Earthing circuit) |
Rated peak withstand current | kA | 50(Main circuit),43,5(Earthing circuit) |
Power frequency withstand voltage(1min) | kV | 42(Phase to earth,phase to phase),48(breaking) |
Lightning impulse withstand voltage | kV | 75(Phase to earth,phase to phase),85(breaking) |
Partial discharge | PC | ≤20 |
Rated sequence of operations of vcbs | O-0.3S-CO-180S-CO | |
Withstands internal arc faults | KA\S | 20/0.5 |
Mechanical life | Times | 10000(VCB) 3000(Isolating switch,Earthing switch) |
Main circuit resistance of each phase | μΩ | 120 |
Earthing switch rated short-circuit making current(peak value) |
KA | 43,5 |
Earthing switch closing times | Times | 2 |
Degree of protection | MPa | IP67(Gas box),IP4X(body case) |
Rated gas pressure(gauge pressure) | MPa | 0.02 |
Minimum operating gas pressure | 0/0 | 0 |
Rated annual leakage rate | ppm | 0.01 |
Moisture content in air box | KV | ≤150 |
Auxiliary circuit power frequency withstand voltage(1min) |
2 |
Rated voltage | kV | 12 |
Rated current | A | 630 |
Rated short-circuit breaking current | kA | 20 |
Rated short-circuit closing current(peak) | kA | 50 |
Rated short-time withstand current3s(rms) | kA | 20 |
Rated peak withstand current | kA | 50 |
Rated sequence of operations | 0.-0.3s-C.0.-180s-C.0. | |
Power frequency withstand voltage(1min) | kV | 42(Phase to earth,phase to phase),48(breaking) |
Lightning impulse withstand voltage(peak) | kV | 75(Phase to earth,phase to phase),85(breaking) |
Partial discharge | PC | ≤5 |
Mechanical life | Times | 10000 |
Main loop resistance per phase | μΩ | ≤110 |
Contact spacing | mm | 9±1 |
Contact pressure over-travel | mm | 3±0, 5 |
Contact final pressure | N | 1800±100N |
Three-phase opening(different phases) | ms | ≤1 |
Contact closure bounce time | ms | ≤2 |
Closing time | ms | ≤70 |
Opening time | ms | ≤60 |
Average opening speed | m/s | 1.1±0.2 |
Average closing speed | m/s | 0.8±0.2 |
Rated number of short-circuit current breaks | Times | 30 |
Rated voltage | kV | 12 |
Rated current | A | 630 |
Rated short-time current 3S(rms) | kA | 20 |
Rated peak withstand current | kA | 50 |
Power frequency withstand voltage(1min) | kV | 42(Phase to earth,phase to phase),48(breaking) |
Lightning impulse withstand voltage(peak) | kV | 75(Phase to earth,phase to phase),85(breaking) |
Three-phase opening(different phases) | mm | ≤2 |
Mechanical life | Times | 3000 |
Total resistance of each phase main circuit | μΩ | ≤60 |
Contact pressure | N | 160+20 |
Closing force | Nm | ≤100 |
Moving and static contact distance | mm | ≥125 |
Rated voltage | kV | 12 |
Rated current | A | 630 |
Rated short-time withstand current 2s(rms) | kA | 17,4 |
Rated peak withstand current | kA | 43.5 |
Power frequency withstand voltage(1min) | kV | 42(Phase to earth,phase to phase),48(breaking) |
Lightning impulse withstand voltage(peak) | kV | 75(Phase to earth,phase to phase),85(breaking) |
Three-phase opening(different phases) | mm | ≤1 |
Mechanical life | Times | 3000 |
Total resistance of each phase main circuit | μΩ | ≤60 |
Contact pressure | N | 160+20 |
Closing force | nm | ≤100 |
Rated short-circuit closing current | KA | 43,5 |
Closing times | Times | 2 |
Moving and static contact distance | mm | ≥125 |
Auxiliary circuit rated voltage | V | DC48,DC110,AC220,DC220 |
Auxiliary circuit power frequency withstand voltage(1min) | kV | 2 |
Opening and closing coil voltage | V | DC48,DC110,AC220,DC220 |
Opening coil current | A | 2 |
Closing coil current Rated voltage energy storage time |
A S |
2 ≤20 |
Auxiliary switch rated voltage | V | DC48,DC110,AC220,DC220 |
Auxiliary switch rated current | A | 10 |
Pairs of the auxiliary switch contact | 80 8C |