Overview & features
These series transformers are with the following characteristics:low loss, low noise, protection against thunder and lighting, high short-circuit withstand capacity and beautiful appearance etc.
Choose us and provide you with satisfactory products!
These series transformers are mainly used in urban and rural power grids and other industrial,mining enterprises,power transmissions and distribution industry and also agricultural projects.
Iron
The iron core is processed by advanced vertical cut, horizontal cut, and stacking with stepped lap core and grade 3 seams.
It disperses the air distribution,improve flucx trend,thus,and decreases the no-load loss,no-load current and noise.
The core uses paticular adhesive for the plate,press ring, and silicon steel surface;and a range of overall structure and measures are used to increase the mechanical strength.
Winding
The winding adopts corrugated oil duct with non-dipping process, bound by shrinkable tape; all windings are of concentric coils; taps of HV winding with corresponding tapping voltage shall be led to the tap switch, and the switch shall be installed on the box cover. Power supply must be cut off first when changing the tapping voltage.
Tank
The tank is bell type or core-lifting type,and the tank side is as corrugated form,with flowing lines,simplicity and beauty.
New structure of HV,LV windings and reasonable layout of oil duct and connecting area increases the capacity of mechanical strength and short-circuit withstand capacity.
Installation of protection device
Transformers of all capacity specifications have been equipped with pressure relief valve;
Gas relay with alarm and tripping terminals is available on request.
Oil-temperature measurement device
All the transformers are equipped with tube holder for glass-stem thermometer that is set on the top of oil tank, and immersed in oil for about 120±10mm;
1000~2000kVA transformer is equipped with outdoor signal thermometer;
Transformer oil tank
Transformer oil tank is composed of corrugated walls with powder painted surface and reinforced with film. Corrugated cooling fin not only has cooling function, but also has "breathing" function, the elasticity of corrugated cooling fin make it adapt to the change of oil volume due to change of temperature. So this hermetically sealed transformer does not have oil conservator, which decreases the height of transformer.
The transformer adopts vacuum oil-injection technology during encapsulation that thoroughly removes the moisture from transformer, and keeps the transformer oil from contacting the air. This technology also avoid insulation performance reduction or oil aging due to entering of oxygen or moisture, it improves operation reliability of transformer.
Service conditions
Installation height: altitude shall not exceed 1000m
Ambient temperature: -40ºC~40ºC
Dimensions & Schematic
630-2500/35 Series Three-phase Double-winding Distribution Transformers with Off-circuit Tap Changer
Rater capacity |
Voltage
Ratio(KV) |
Vector Group |
Loss values for
S9 serial
transformer |
Loss values for
s11 serial
transformer |
Loss values fon S11
serial transformer |
Current |
Impedance |
Weight |
Outline Dimension |
Gauge |
(kVA) |
HV |
LV |
|
No-load
loss |
Full-load
loss |
No-load
loss |
Full-load
loss |
No-load
loss |
Full-load Loss |
(%) |
(%) |
oil weight |
Total weight |
L |
W |
H |
(mm) |
630 |
35 38.5±5% or 2×2.5% |
6.3 6.6 10 05 11 |
Yd11 |
1.04 |
8.28 |
0.94 |
7.87 |
0.83 |
7.78 |
1.1 |
6.5 |
0.65 |
2.9 |
2100 |
1300 |
2300 |
820 |
800 |
1.23 |
9.9 |
1.11 |
9.4 |
0.98 |
9.4 |
1 |
0.7 |
3.2 |
2200 |
1350 |
2350 |
820 |
1000 |
1.44 |
12.15 |
1.3 |
11.54 |
1.15 |
11.54 |
1 |
0.85 |
3.5 |
2350 |
1450 |
2400 |
820 |
1250 |
1.76 |
14.67 |
1.58 |
13.94 |
141 |
13.94 |
0.9 |
1.01 |
3.84 |
2500 |
1600 |
2450 |
1070 |
1600 |
2.12 |
17.55 |
1.91 |
16.67 |
1.7 |
16.67 |
0.8 |
1.2 |
5 |
2600 |
1700 |
2500 |
1070 |
2000 |
2.72 |
19.35 |
2.45 |
18.38 |
2.18 |
18.38 |
0.7 |
1.28 |
6 |
2730 |
1800 |
2600 |
1070 |
2500 |
3.2 |
20.7 |
2.88 |
19.67 |
2.56 |
19.67 |
0.6 |
1.4 |
7 |
2870 |
1900 |
2700 |
1070 |
It is made by advanced assembling lines and method,with qualified and refined accessories.
It enjoys four remote functions:
1.remote communication |
2.remote test |
3.remote adjustment |
4.remote control |
Application
These series transformers have passed the identification test by state bureau of machinery industry,and state power corporation.
ABOUT OUR COMPANY
a).HONLE Electronic co.,Ltd is specified in producing Single phase and three phase voltage stabilizers, voltage regulator, distribution transformers, low-voltage switch gear assembly,complete plant equipment
b)Passed the ISO9001 quality management system certification
c).HONLE insist on the quality of survival ,innovation and development all the time , try our best to be winner to give you the competitive product .