Customization: | Available |
---|---|
Type: | Power Source Arrester |
Structure: | Zinc Oxide Arrester |
Still deciding? Get samples of US$ 29/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Code No. | Rated Voltage | MCOV | Current impulse Residual Voltage | Long impulse withstand current 2000 us |
High current impulse withstand |
||
1/4μs Steep current impulse | 8/20μs Lightning current impulse | 30/60μs Switching current impulse |
|||||
KV(rms) | KV(rms) | KV(crest) | KV(crest) | KV(crest) | |||
YH5W-3 | 3 | 2.55 | 11.3 | 9 | 8.9 | 150 | 65 |
YH10W-3 | 3 | 2.55 | 11.3 | 9 | 8.9 | 250 | 100 |
Code No. | Rated Voltage | MCOV | Current impulse Residual Voltage | Long impulse withstand current 2000 us |
High current impulse withstand |
||
1/4μs Steep current impulse | 8/20μs Lightning current impulse | 30/60μs Switching current impulse |
|||||
KV(rms) | KV(rms) | KV(crest) | KV(crest) | KV(crest) | |||
YH5W-6 | 6 | 5.1 | 22.6 | 18 | 16.8 | 150 | 65 |
YH10W-6 | 6 | 5.1 | 22.6 | 18 | 16.8 | 250 | 100 |
Code No. | Rated Voltage | MCOV | Current impulse Residual Voltage | Long impulse withstand current 2000 us |
High current impulse withstand |
||
1/4μs Steep current impulse | 8/20μs Lightning current impulse | 30/60μs Switching current impulse |
|||||
KV(rms) | KV(rms) | KV(crest) | KV(crest) | KV(crest) | |||
YH5W-9 | 9 | 7.65 | 33.7 | 27 | 23.8 | 150 | 65 |
YH10W-9 | 9 | 7.65 | 33.7 | 27 | 23.8 | 250 | 100 |
Manufacturer | HONLE GROUP CO.,LTD | |||||||
Rated Voltage | kV | 3 | 6 | 9 | 12 | 15 | 18 | |
Nominal discharge current | kA | 5 | 5 | 5 | 5 | 5 | 5 | |
1 | General Feature | Unit | ||||||
1.1 | Applicable standard | IEC60099-4(2004) | ||||||
1.2 | Type designation | YH5W-3 | YH5W-6 | YH5W-9 | YH5W-12 | YH5W-15 | YH5W-18 | |
1.3 | Housing material | Silicone rubber | Silicone rubber | Silicone rubber | Silicone rubber | Silicone rubber | Silicone rubber | |
1.4 | With(out) gqps | Without | Without | Without | Without | Without | Without | |
2 | Ratings & characteristics | |||||||
2.1 | Rated frequency | Hz | 50/60 | 50/60 | 50/60 | 50/60 | 50/60 | 50/60 |
2.2 | Residual voltage at | |||||||
-lightning impule 8/20μs | kV | 8.5 | 17 | 25.5 | 34 | 42.5 | 51 | |
-steep current impulse 1/10μs | kV | 9.8 | 19.6 | 29.4 | 39.2 | 49 | 58.8 | |
-switching impulse 30/60μs(10kA&up) | kV | 7.3 | 14.6 | 21.9 | 29.4 | 36.6 | 43.9 | |
-switching wave(class 1&up) | kA | 0.5 | 0.5 | 0.5 | 0.5 | 0.5 | 0.5 | |
2.3 | Continuous operating voltage | kV | 2.55 | 5.1 | 7.65 | 9.6 | 12.7 | 15.3 |
2.4 | Power freqncy reference voltage | kV | ≥3 | ≥6 | ≥9 | ≥12 | ≥15 | ≥18 |
2.5 | Long duration current impulse withstand | |||||||
-2ms rectangular current withstand | A | 150 | 150 | 150 | 150 | 150 | 150 | |
2.6 | Operating duty | |||||||
-4/10μs high current impulse withstand | kA | 65 | 65 | 65 | 65 | 65 | 65 | |
2.7 | Housing insulation level | |||||||
-lightning impulse | kV | 15 | 30 | 40 | 50 | 70 | 80 | |
-power frequency,wet 1 min | kV | 10 | 15 | 30 | 30 | 35 | 40 | |
2.8 | Partial discharge | pC | ≤10 | |||||
2.9 | Power frequency voltage versus time | 1.15UR-0.1s 1.10UR-1s 1.05UR-1s 1UR-1200s | ||||||
2.10 | Other ratings & characteristics | |||||||
-torsional | Nm | 60 | 60 | 60 | 60 | 60 | 60 | |
2.11 | creepage distance/rated voltage ratio(General) | kV/mm | ≥25 | ≥25 | ≥25 | ≥25 | ≥25 | ≥25 |
-Long protection distance
-High energy input capacity
-Stable U-I characteristic even after multiple strokes
-Proof against ageing
-Explosion and shatter-resistant design
-Pollution resistant and UV-stable
-Housing resistant to rough handling
-Maintenance free
-Stable against shock and vibration
-High mechanical resistance
FACTORY