• Flrn36-12/24 Indoor Sf6 Switch Disconnector Load Break Switch Lbs
  • Flrn36-12/24 Indoor Sf6 Switch Disconnector Load Break Switch Lbs
  • Flrn36-12/24 Indoor Sf6 Switch Disconnector Load Break Switch Lbs
  • Flrn36-12/24 Indoor Sf6 Switch Disconnector Load Break Switch Lbs
  • Flrn36-12/24 Indoor Sf6 Switch Disconnector Load Break Switch Lbs
  • Flrn36-12/24 Indoor Sf6 Switch Disconnector Load Break Switch Lbs

Flrn36-12/24 Indoor Sf6 Switch Disconnector Load Break Switch Lbs

Type: High-voltage
Installation: Fix
Operation: Manual/Motor
Grounding Mode: Grounding
Number of Poles: Three Pole
Structure of Operating: Electric
Customization:

360° Virtual Tour

Diamond Member Since 2014

Suppliers with verified business licenses

Rating: 5.0/5

Basic Info.

Model NO.
FLRN36
Certification
ISO
Brand
Honle
Delivery
30-45days
Transport Package
Export Standard Packing
Trademark
Honle
Origin
Wenzhou, Zhejiang
Production Capacity
500000pieces/Year

Product Description

Flrn36-12/24 Indoor Sf6 Switch Disconnector Load Break Switch Lbs
Summary

FLRN36 indoor AC high-voltage load break switch-fuse combination (combination in short)is a comprehensive and new combination app aratus produced on the bases of the mature experience in domestic and abroad. It is a complement apparatus of HXGN15-12/24 AC metal-enclosed ring main unit and it meet requirement of users in different power system. It has the advantages such as simple structure, easy maintenance, strong arc-extinction capability, high gap insulating level and high reliability. It accords with IEC62271-105, GB16926 & GB/T 11022 standards.

Ambient condition
 
1. Altitude: ≤1000m;
2. Ambient temperature: -25ºC ~+40ºC ;
3. Relative humidity: daily average≤95% , monthly average≤90% ;
4. Earthquake intensity: ≤8 degree;
5. Occasions without flammable and explosive matter, without corrosive chemical and frequent severe vibration

 

Item NO. Name Unit Technical parameters
Load break switch panel
1 Rated Voltage Un kV 12 24 36
2 Rated Frequency Hz 50 50 50
3 Rated Current A 630 630 630
4 Rated Load Breaking Current A 630 630 630
5 Rated Short Time Withstand Current(rms) kA 20 20 20
6 Rated Short Time Duration s 3 3 3
7 Rated Peak Withstand Current  kA 50 50 50
8 Rated Closed Switch - Off Current A 630 630 630
9 Rated Cable Charging Breaking Current A 10 10 10
10 Rated Active Load Breaking Current A 630 630 630
13 Earthing Switch 2s Short Time Withstand Current  kA 20 20 20
14 Rated Short-Circuit Current Making Times  times 2 2 2
15 Rated Current Breaking Times times 10 10 10
16 Mechanical Endurance  Load Break Switch times 3000 3000 3000
Earthing Switch times 2000 2000 2000
17 SF6 gas anual leakage rate≤ /year 0.10% 0.10% 0.10%
18 Rated Insulation Level Unit Technical parameters
1min Power Frequency withstand voltage(rms) On isolating distance kV 48 60 110
Phase to Phase  kV 42 50 85
Phase to Earth kV 42 50 85
Lightning impulse withstand voltage(peak) On isolating distance kV 85 145 215
Phase to Phase  kV 75 125 185
Phase to Earth kV 75 125 185


Flrn36-12/24 Indoor Sf6 Switch Disconnector Load Break Switch LbsFlrn36-12/24 Indoor Sf6 Switch Disconnector Load Break Switch Lbs
Flrn36-12/24 Indoor Sf6 Switch Disconnector Load Break Switch Lbs

 

 
Flrn36-12/24 Indoor Sf6 Switch Disconnector Load Break Switch Lbs

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now

You Might Also Like

360° Virtual Tour

Diamond Member Since 2014

Suppliers with verified business licenses

Rating: 5.0/5
Registered Capital
16.52 Million USD
Plant Area
35000 square meters
Management System Certification
ISO9001:2015, ISO14001:2015, ISO45001:2018 certificate