Honle Modeloutdoor Oil-Immerse Potential Transformer

Phase: Single
Winding Form: Multilayer Honeycomb Type
Installation: Active Type
Voltage Transformation Principle: Photoelectric Type
Magnetic Circuit Structure: Combined Type
Insulating Medium: Insulating Oil
Samples:
US$ 100/Piece 1 Piece(Min.Order)
| Request Sample
Customization:

360° Virtual Tour

Diamond Member Since 2014

Suppliers with verified business licenses

Rating: 5.0/5

Basic Info.

Model NO.
JDJJ2-11
Transport Package
Standard
Trademark
HONLE
Origin
Zhejiang, China
HS Code
8504311000
Production Capacity
3000PCS Per Month

Product Description

JDJJ2-11 Potential Transformer

 

1. Application

Series JDJJ2 of non-earthed voltage transformer is single-phase, oil-immersed. It's designed for voltage, electric energy measurement and relay protection in a ineffectively earthed neutral point power system with rated frequency of 50Hz and rated voltage of 11kV.
2. Type Designation
J   D   J   J   2  - 11

3. Service Condition
  • Altitude: up to 1000m above sea level;
  • Ambient temperature: -25ºC to +40ºC;
  • Relative humidity: 85%,at 20ºC
Honle Modeloutdoor Oil-Immerse Potential Transformer

 

4. Construction
The voltage transformer is single-phase, three-winding and core type. The active parts are attached to tank cover and put in square oil-tank. The terminals of windings are led out of tank through HV and LV bushings respectively. The conservator is located on the top of HV bushing on which primary terminal is fixed and provided with rubber diaphragm inside to avoid oil from contacting with air. The conservator is fitted with oil level gauge. The tank is provided with drain valve at bottom and mounting holes on the base for fixing. Oil tank and bushing, filled with transformer oil is oilpaper-insulated structure and the conservator is.
5. Technical Data
Performance conforms to IEC-186 standard and GB1207-1997 "Voltage transformer".
Rated primary voltage:11000/3V;
Rated secondary voltage:110/3V;
Rated primary current :15,20,30,40,50,75,100,150,200,300,400,600,700 and 1000
Rated secondary current 5A
Rated voltage of residual voltage winding:110/3V;
Rated voltage factor and duration:1.9;  8h.
The rated output of secondary winding and corresponding accuracy class: 150VA class 0.5, 250VA class1, 500VA class3.
Max. Output: 1000VA;
Residual voltage winding is 100VA and class 6P;
Rated insulation level:
Power frequency withstand voltage:95kV;
Lightning impulse withstand voltage: Full wave, 185kV Chopped wave, 220kV.
The voltage transformer is able to operate continuously under 1.2 times rated primary voltage.

Table 1. The relationship between rated secondary load and accuracy grade
Specification and model Accuracy grade or no Rated secondary load(Ω)
0.5grade 1grade 3grade 10grade
JDJJ2-11-0.5/3 0.5 2 4 - -
JDJJ2-11-D/0.5
JDJJ2-11-0.5/1
JDJJ2D-11-D/0.5
0.5 1.2 3   -
JDJJ2-11-0.5/1 1   1.2 3 -
JDJJ2-11-0.5/3 3     2 4
JDJJ2-11-D/0.5 D   1.2 3 -
Table 2.10% multiple of this type of PT
         The maximum current multiple of this type of PT
6.Factory
Honle Modeloutdoor Oil-Immerse Potential TransformerHonle Modeloutdoor Oil-Immerse Potential Transformer

Honle Modeloutdoor Oil-Immerse Potential Transformer

 

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now

You Might Also Like

360° Virtual Tour

Diamond Member Since 2014

Suppliers with verified business licenses

Rating: 5.0/5
Registered Capital
16.52 Million USD
Plant Area
35000 square meters
Management System Certification
ISO9001:2015, ISO14001:2015, ISO45001:2018 certificate