• Honle S9 Series Hemetically Sealed Oil-Immersed Power Transfomer
  • Honle S9 Series Hemetically Sealed Oil-Immersed Power Transfomer
  • Honle S9 Series Hemetically Sealed Oil-Immersed Power Transfomer
  • Honle S9 Series Hemetically Sealed Oil-Immersed Power Transfomer
  • Honle S9 Series Hemetically Sealed Oil-Immersed Power Transfomer
  • Honle S9 Series Hemetically Sealed Oil-Immersed Power Transfomer

Honle S9 Series Hemetically Sealed Oil-Immersed Power Transfomer

Application: Power
Phase: Three
Core: Core-type Transformer
Cooling Method: Oil-immersed Type Transformer
Winding Type: Multi-winding Transformer
Certification: ISO9001-2000, ISO9001, CCC
Samples:
US$ 2450/Piece 1 Piece(Min.Order)
| Request Sample
Customization:

360° Virtual Tour

Diamond Member Since 2014

Suppliers with verified business licenses

Rating: 5.0/5
  • Overview
  • STRUCTURAL FEATURES
  • IRON CORE
  • Winding
Overview

Basic Info.

Model NO.
S9
Usage
Power Transformer
Frequency Characteristics
High Frequency
Brand
Honle
Use Environment
Petroleum /Metallurgy/Chemical Industry
Transport Package
Standard Export Package
Trademark
HONLE
Origin
Zhejiang, China(Mainland)
HS Code
8504401990
Production Capacity
50PCS/Month

Product Description

 



Honle S9 Series Hemetically Sealed Oil-Immersed Power Transfomer

STRUCTURAL FEATURES
Honle S9  Series  Hermetically Sealed Oil Immersed Transformer Distribution Power Transformer
 

It is suitable for power systems of AC50Hz and rated working voltage up to and including 10kV,can be used as distribution transformer for petroleum,metallurgy ,chemical industry ,textile industry ,light industry,etc.

 
IRON CORE

The iron core is made of cold-rolled grain-oriented silicon steel sheets with high magnetic conductivity,with inclined joint laminated structure.section of the core limbs is of multi-class ladder round,with uniform section with that of yoke.

Winding

The winding adopts corrugated oil duct with non-dipping process,bound by shrinkable tape;all winding are of concentric coils;taps of HV winding with corresponding tapping voltage shall be led to the tape switch,and the switch shall be installed on the box cover.Power supply must be cut off first when changing the tapping voltage.

 

Service conditions
1.Installation height: altitude shall not exceed 1000m
2.Ambient temperature:-40ºC~40ºC

Main technical parameters

S9-M 6-10kv 

Rated capacity Voltage combination Connection group Loss(KW) No-load current Short-circuit impedance Weight(kg)
(kVA) HV High-voltage tapping range LV(kV) Symbal No-load On-load (%) (%) Oil weight Gross weight
30 6
6.3
10
10.5
11
±5%
 
0.4 Dyn11
Yzn1
Yyn0
0.13 0.63/0.60 2.3 4.0 75 295
50 0.17 0.91/0.87 2.0 88 395
63 0.20 1.09/1.04 1.9 95 420
80 0.25 1.31/1.25 1.9 103 480
100 0.29 1.58/1.50 1.8 115 540
125 0.34 1.89/1.80 1.7 130 645
160 0.40 2.31/2.20 1.6 145 740
200 0.48 2.73/2.60 1.5 175 885
250 0.56 3.20/3.05 1.4 195 1010
315 0.67 3.83/3.65 1.4 230 1205
400 0.80 4.52/4.30 1.3 255 1375
500 0.96 5.41/5.15 1.2 4.5 285 1620
630 Dyn11
Yyn0
1.20 6.20 1.1 350 1960
800 1.40 7.50 1.0 405 2310
1000 1.70 10.30 1.0 490 2690
1250 1.95 12.00 0.9 550 3315
1600 2.40 14.50 0.8 625 3985

Please provide the product model, rated capacity, high and low voltage rated voltage and high voltage tapping range, phase number, frequency, and connection group label when ordering.
Company
Honle S9 Series Hemetically Sealed Oil-Immersed Power Transfomer

Honle S9 Series Hemetically Sealed Oil-Immersed Power TransfomerHonle S9 Series Hemetically Sealed Oil-Immersed Power Transfomer

 

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now

You Might Also Like

360° Virtual Tour

Diamond Member Since 2014

Suppliers with verified business licenses

Rating: 5.0/5
Registered Capital
16.52 Million USD
Plant Area
35000 square meters
Management System Certification
ISO9001:2015, ISO14001:2015, ISO45001:2018 certificate